Siemens LMV27 Series Burner Management Controls

Siemens LMV27 Series is a microprocessor-based burner management system for industrial gas or oil forced-draft burners operating in intermittent mode. The LMV27.100A2 combines electronic fuel-air ratio control, flame supervision, gas valve proving, and burner sequencing in one unit. It supports up to two compatible SQM3 or SQN1 actuators, Siemens AZL2 display units, ACS410 configuration software, and Modbus communication through an OCI412.10 interface. Suitable for industrial boilers and process heating systems requiring coordinated combustion control.

Product Description

Siemens Burner Controls LMV27 Series

Siemens LMV27 Series is a microprocessor-based burner management system engineered for the safe sequencing, operation, and flame supervision of industrial forced-draft burners using gas or oil. It is designed for single-fuel burners operating in intermittent mode.

The LMV27.100A2 integrates electronic fuel-air ratio control, burner safety functions, and gas valve proving within a single control platform. With support for up to two compatible SQM3 or SQN1 actuators, it enables coordinated positioning of combustion air and fuel control components in industrial boiler and heating applications.

Key Features

  • Microprocessor-controlled burner management and safety sequencing
  • Designed for single-fuel gas or oil burners in intermittent operation
  • Integrated electronic fuel-air ratio control
  • Supports up to two SQM3 or SQN1 actuators
  • Integrated gas valve proving function
  • Flame supervision with compatible QRA2, QRA4, QRA10, QRB, QRC or ionization detectors
  • Modbus communication using the OCI412.10 interface
  • Burner Communication Interface (BCI) for external display or PC connection
  • Parameter configuration using AZL2 display units or Siemens ACS410 software

Industrial Applications

Siemens LMV27 is intended for burner OEM manufacturers and qualified system integrators. Typical applications include:

  • Industrial steam boiler systems
  • Industrial gas burner installations
  • Industrial oil burner installations
  • Industrial process heating equipment
  • Forced-draft combustion systems
  • Burners requiring coordinated fuel and combustion air control

Compatible System Components

  • Display Units: Siemens AZL21 and AZL23
  • Actuators: Siemens SQM33 and SQN1 Series
  • Flame Detectors: QRA2, QRA4, QRA10, QRB, QRC and ionization probes, depending on the application
  • PC Software: Siemens ACS410
  • Communication Interfaces: OCI410 for PC connection and OCI412.10 for Modbus

Available Model

  • LMV27.100A2: AC 230 V, European parameter set, gas safety time 3 seconds and oil safety time 5 seconds

Selection Guidance: Confirm the supply voltage, burner fuel type, flame detector, actuator compatibility, operating sequence and safety requirements before installation. Configuration and commissioning must be carried out by qualified personnel in accordance with Siemens technical documentation.

Specifications

Siemens LMV27 Technical Specifications

BrandSiemens
Product SeriesLMV27 Series
Reference ModelLMV27.100A2
Product TypeBurner Management System
Control TechnologyMicroprocessor-based
Fuel TypeGas / Oil (Single-fuel Burner)
Operating ModeIntermittent Operation
Supply VoltageAC 230 V (-15% / +10%)
Frequency50 / 60 Hz ±6%
Power Consumption<30 W (Typical)
Fuel/Air Ratio ControlElectronic
Maximum Actuators2
Compatible ActuatorsSQM3... / SQN1...
Gas Valve ProvingIntegrated
Flame DetectorsQRA2 / QRA4 / QRA10 / QRB / QRC / Ionization Probe
Safety Time (Gas)3 seconds
Safety Time (Oil)5 seconds
CommunicationBCI / Modbus via OCI412.10
Display UnitsAZL21 / AZL23
Configuration SoftwareSiemens ACS410
InterfacesOCI410 / OCI412.10
Protection RatingIP00 (Basic Unit)
Required Installation ProtectionIP40
Operating Temperature-20 to +60 °C
Relative Humidity<95% RH (Non-condensing)
Internal Fuse6.3 AT
Maximum External Fuse16 AT
Applicable StandardsEN 298, EN 1643, EN 12067-2, EN 13611

Available Model Specifications

Model Supply Voltage Parameter Set Safety Time (Gas) Safety Time (Oil)
LMV27.100A2 AC 230 V (-15% / +10%) European 3 s 5 s

Technical Note: Specifications refer to Siemens Datasheet CC1N7541en for LMV27.100A2. The burner or boiler manufacturer must ensure IP40 protection through suitable installation. Component compatibility and commissioning settings must be verified against the applicable Siemens documentation.