Siemens LEC1 Series Industrial Burner Controllers

Siemens LEC1 Series burner control units are designed for automatic startup, ignition sequencing and supervision of industrial forced-draft gas, oil and dual-fuel burners. Supporting double-flame and multiflame monitoring, LEC1 works with separate Siemens LAE10, LFE10 or LFE50 flame safeguards according to the detector and operating mode. Features include adjustable prepurge time of 8–63 seconds, configurable safety times of 0–9 seconds, air damper control, air pressure supervision, safety lockout and remote reset. Suitable for maintenance and replacement of compatible industrial boiler and heating systems. Siemens specifies LEC1 for existing applications rather than new designs.

Product Description

Siemens Burner Controllers LEC1 Series

Siemens LEC1 Series are industrial burner control units developed for automatic startup, ignition sequencing and supervision of forced-draft oil, gas and dual-fuel burners. The controllers support double-flame and multiflame supervision, with continuous or intermittent operation depending on the selected flame safeguard.

LEC1 is used with separate Siemens flame safeguards such as LAE10, LFE10 and LFE50. The controller manages the burner program, fan motors, air damper, ignition transformer, fuel valves and associated safety functions, while the connected flame safeguard evaluates the flame signal.

Key Features

  • Automatic burner startup and operating sequence control
  • Double-flame and multiflame supervision with separate flame safeguards
  • Adjustable prepurge time from 8 to 63 s
  • Adjustable first and second safety times from 0 to 9 s
  • Automatic air damper control with optional postpurge
  • Air pressure switch monitoring and functional checks before startup
  • Direct ignition or pilot burner configurations according to system design
  • Automatic extraneous-light supervision during off and purge periods
  • Safety lockout on specified flame or air pressure failures
  • Built-in lockout warning lamp and electrical remote reset
  • Operating program and fault phase visible through the viewing window

Compatible Siemens Flame Safeguards

Flame SafeguardDetector / ApplicationOperating Mode
LAE10RAR photocell detector for oil burnersIntermittent
LFE10Ionization probe for gas burners or QRA UV detector for gas, oil and dual-fuel burnersIntermittent
LFE50QRA50 / QRA51 UV detectors for gas, oil and dual-fuel burnersContinuous / Intermittent

Operating Principle

After receiving a heat demand, LEC1 verifies the required safety conditions and initiates the burner startup sequence. Prepurging, air damper positioning and ignition occur according to the configured program. The connected flame safeguard must confirm flame establishment within the specified safety time.

Depending on the burner configuration, LEC1 can control the fan motor, flue gas fan, air damper, ignition transformer, up to three fuel valves, load controller and external fault signaling equipment.

Typical Applications

  • Industrial steam and hot water boilers
  • Forced-draft gas and oil burners
  • Dual-fuel industrial combustion systems
  • Dual-flame and multiflame installations
  • Industrial process heating equipment
  • Maintenance and replacement of compatible existing burner controls

Selection and Replacement Guidelines

Verify the complete LEC1 type reference, mains voltage, frequency, flame safeguard, detector type, prepurge and safety times, fuel valve sequence, air damper arrangement, terminal base and wiring before replacement.

Important: Siemens states that LEC1 should not be used for new designs. The correct operating mode depends on the connected flame safeguard. All installation, adjustment and commissioning work must be performed by qualified personnel according to Siemens technical documentation.

Specifications

Siemens LEC1 Series Technical Specifications

SpecificationTechnical Data
BrandSiemens
Product SeriesLEC1 Series
Product TypeIndustrial Burner Control Unit
Burner TypeForced-Draft Oil / Gas / Dual-Fuel Burners
Flame SupervisionDouble-Flame / Multi-Flame using separate safeguards
Operating ModeContinuous / Intermittent, depending on flame safeguard
Rated VoltageAC 220–240 V or AC 100–110 V, model-dependent
Mains Frequency50–60 Hz ±6%
Power Consumption - Startup8 VA
Power Consumption - Operation5 VA
Built-in FuseT6.3H250V
External FuseMax. 10 A (Slow)
Output Load per TerminalMax. 4 A (AC3)
Total Output LoadMax. 5 A (AC3)
Prepurge Time (t1)Adjustable: 8–63 s
First Safety Time (TSA)Adjustable: 0–9 s
Second Safety Time (t9)Adjustable: 0–9 s
Air Damper ControlAutomatic control with optional postpurge
Air Pressure SupervisionAir pressure switch monitoring where configured
Protection RatingIP40 when correctly mounted
Operating Temperature-20 to +60 °C
Transport Temperature-50 to +60 °C
Relative Humidity<95% RH, non-condensing
Installation AltitudeMax. 2,000 m above sea level
WeightApprox. 2 kg
Mounting PositionAny orientation
Compatible Flame SafeguardsLAE10 / LFE10 / LFE50
Terminal BaseAGG41041713 (EC) / AGG12.1, ordered separately
Designed Lifetime250,000 burner startup cycles or approx. 10 years under specified conditions
Technical ReferenceSiemens CC1N7761en (21.08.2018)

Flame Safeguard Compatibility

ModelFlame DetectorOperation
LAE10RAR PhotocellIntermittent
LFE10Ionization Probe / QRA UVIntermittent
LFE50QRA50 / QRA51 UVContinuous / Intermittent

Technical Note: The first and second safety times must be set according to the burner application and applicable safety requirements. Continuous operation requires a suitably rated flame safeguard. Siemens identifies LEC1 as unsuitable for new designs. Verify the exact type reference, factory settings and connection diagram before installation or replacement.