Siemens LGA Series Gas Burner Controllers

Siemens LGA Series gas burner controllers provide automatic startup, ignition sequencing, gas valve control and ionization flame supervision for small- to medium-capacity atmospheric gas burners operating intermittently. The series includes LGA41, LGA52 and LGA63, with two gas valve outputs (BV1/BV2), safety lockout and integrated manual reset. Auxiliary fan and air pressure switch connections are provided on selected versions, while undervoltage monitoring depends on the exact model. Designed primarily for maintenance and replacement of compatible existing gas-fired heating systems; Siemens recommends LME burner controls for new installations.

Product Description

Siemens Burner Controllers LGA Series

Siemens LGA Series are automatic gas burner controls designed for startup, ignition sequencing and flame supervision of small- to medium-capacity atmospheric gas burners operating intermittently.

The controllers manage the ignition transformer and gas valve sequence while supervising the flame through an ionization probe. The series uses an electromechanical thermal sequencing mechanism with electronic flame supervision.

Key Features

  • Automatic burner startup and ignition sequencing
  • Ionization probe flame supervision
  • Two gas valve control outputs: BV1 and BV2
  • Safety lockout for ignition failure and abnormal flame signals
  • Auxiliary fan and air pressure switch connections on selected models
  • Model-dependent undervoltage detection
  • Integrated lockout indication lamp and manual reset button
  • Plug-in design for servicing and replacement
  • Replacement of compatible LFI7 and LFI5 predecessors using specified adapters

Operating Principle

Following a startup command, the controller initiates its model-specific ignition program. It energizes the ignition equipment and releases the appropriate gas valves while monitoring the flame signal.

When a valid ionization signal is detected, burner operation continues according to the control sequence. If flame establishment fails within the specified safety time (TSA), the controller initiates safety lockout.

Available Series

  • LGA41: Atmospheric gas burner control without auxiliary fan connection. The available variants have different safety times and undervoltage functions.
  • LGA52: Gas burner control family; LGA52.171B27 supports auxiliary fan and air pressure switch connections, while LGA52.150B17/B27 do not.
  • LGA63: LGA63.191A27 supports auxiliary fan and air pressure supervision, undervoltage detection and enhanced flame signal sensitivity.

Typical Applications

  • Existing small and medium-capacity gas burners
  • Gas-fired industrial heating equipment
  • Intermittently operated gas combustion systems
  • Maintenance and replacement of compatible legacy burner controllers
  • Air heating equipment on specified variants

Model Selection and Replacement

Siemens specifies that LGA burner controls should not be used for new designs and recommends considering LME1, LME2, LME3 or LME4 for new applications.

Before replacement, verify the full model number, voltage, ignition safety time, wiring, flame detector, fan and air pressure switch configuration, and compatible plug-in base.

Safety Notice: Installation and commissioning must be carried out by qualified personnel following Siemens technical documentation and applicable safety regulations.

Specifications

Siemens LGA Series Technical Specifications

SpecificationTechnical Data
BrandSiemens
Product SeriesLGA Series
Product TypeGas Burner Controls
ApplicationSmall to medium-capacity atmospheric gas burners, intermittent operation
Supply VoltageAC 220-240 V or AC 100-110 V, model-dependent; LGA63: AC 230 V ±10%
Mains Frequency50-60 Hz ±6%
Power Consumption3 VA
Input Current at Terminal 1Max. 5 A
Flame DetectionIonization Probe
Minimum Detector Current5 µA
Maximum Possible Detector Current100 µA
Detector Cable LengthMax. 20 m (separate cable)
Minimum Insulation Resistance50 MΩ
Gas Valve Outputs2 (BV1 and BV2)
Auxiliary Fan / Air Pressure SwitchLGA52.171B27 / LGA63.191A27
Undervoltage DetectionModel-dependent; not provided on LGA41.153A27
Degree of ProtectionIP40 when integrated correctly
Operating Temperature0 to +60 °C; LGA41.173A27 / LGA52.171B27: -20 to +60 °C
Relative Humidity<95% RH
WeightApprox. 180 g
Mounting TypePlug-in
Compatible Plug-in BaseAGK11 Series (accessory)
Reference DocumentSiemens CC1N7418en (21.06.2016)

Model Variants and Ignition Safety Time

ModelSupply VoltageSafety Time (TSA)
LGA41.153A27AC 220-240 V5 s
LGA41.173A27AC 220-240 V10 s
LGA52.150B27AC 220-240 V5 s
LGA52.150B17AC 100-110 V5 s
LGA52.171B27AC 220-240 V4.5-7.5 s
LGA63.191A27AC 230 V10 s

Timing Note: Values apply at AC 220 V or AC 110 V according to model. Siemens specifies a timing multiplier of 0.7 when operating at AC 240 V. Check maximum permitted safety time separately from the nominal TSA values.

Selection Note: LGA is not recommended for new designs. Check the complete model number, operating sequence and installation conditions before replacing an existing controller.